Article

July 31, 2026

Risk Management in the Sectorization of the Water Distribution Network in a Brazilian Public University

Iany Andrade dos Santos; Márcia Aparecida Prim

DOI: 10.22167/2675-6528-202600902

Article prepared by the ResumeAI tool, an artificial intelligence solution developed by the Pecege Institute focused on synthesis and writing.

Abstract

The zoning of water distribution networks represents a crucial strategy for loss control and the improvement of hydraulic efficiency; however, its implementation in institutional environments, such as public universities, involves technical, operational, and management risks that can compromise the project’s objectives. The study aimed to identify, analyze, and classify the risks associated with the zoning of the water distribution network in a Brazilian public university, proposing mitigation strategies to enhance operational efficiency and the security of the institutional supply system. The research was characterized as applied, exploratory, and descriptive, with a qualitative approach and quantitative support, configuring itself as a case study. Data collection involved a systematic literature review, institutional document analysis, and a survey of specialists through a structured form. The identified risks were classified using a probability and impact matrix, according to PMBOK guidelines. 22 risks were identified, distributed across five categories, with one critical risk (R22 – topographic inconsistency/unmapped interconnections) and 12 high risks, indicating a profile of distributed vulnerability. The analysis revealed that the risks were not restricted to technical aspects but included structural weaknesses, operational limitations, and institutional challenges. The proposed mitigation plan organized actions into short, medium, and long-term time horizons, demonstrating that significant progress can be achieved through institutional organization and integrated planning, without exclusive reliance on high financial investments. The research contributed a structured risk mapping and methodological subsidies for the management of similar projects.

Keywords: institutional supply; water infrastructure; probability and impact matrix; mitigation; PMBOK.

1. Introduction

The management of urban water resources constitutes a growing challenge on a global scale, exacerbated by rapid urbanization and the aging of supply infrastructures. In several urban centers, the capacity of water distribution systems is compromised, resulting in intermittent supply and operational inefficiencies (Tucci, 2008; UNESCO, 2020). This problem is particularly pronounced in developing countries, where infrastructure often does not keep pace with population growth and demand, leading to situations of shortage (Saldarriaga et al., 2025). One of the most critical factors contributing to this inefficiency is the high rate of water losses, which can range from twenty to thirty percent of the water produced, reaching levels above fifty percent in old or poorly maintained networks (El-Zahab and Zayed, 2019; Elshazly et al., 2024). Such losses not only represent a waste of a vital resource but also entail substantial economic impacts, such as high costs of abstraction, treatment, and pumping, as well as damage to urban infrastructure. The mitigation of these losses is, therefore, imperative for the economic feasibility and environmental sustainability of supply systems.

Given this panorama, the sectorization of water distribution networks emerges as a fundamental strategy for effective monitoring and control. This technique consists of dividing the network into smaller, hydraulically isolated areas, allowing for more precise control of variables such as pressure and flow rate (El-Zahab and Zayed, 2019). Sub-sectorization facilitates the detection and localization of leaks, optimizes the use of meters, and enables proactive management of losses, contributing significantly to the improvement of the hydraulic and operational efficiency of the systems (Sela Perelman et al., 2015). However, the scientific literature still presents a significant gap regarding its application and associated risks in specific institutional environments, such as university campuses. These contexts have unique characteristics, such as complex and often old distribution networks, large territorial size, and varied water demands, requiring an adapted investigative approach.

The implementation of a sectorization project in a water distribution network, especially in a complex institutional environment, is an undertaking of high complexity. In this sense, the application of robust project management practices, as advocated by the Project Management Institute (PMI, 2021), is crucial to ensure the achievement of objectives. Risk management, in particular, plays a central role, as risk is inherent to any project and represents the uncertainty of an event or condition that, if it occurs, can have positive or negative effects on the project objectives (PMI, 2021). The university campus object of this study exemplifies this complexity. The institution underwent a significant transformation in its water supply system starting in mid-two thousand and twenty-four, opting to implement its own system based on tubular wells and a self-managed internal network, in response to regulatory and tariff changes. However, the internal distribution network, over fifty years old, already had a history of recurring problems, including pipe bursts and valve failures. This coexistence between a newly implemented production system and an aging distribution infrastructure created an environment of amplified risk. The need for temporary suspensions of academic activities, rationing in specific sectors, and the use of water trucks, recorded in the initial phase of operation, highlighted significant vulnerabilities in the system’s capacity to maintain acceptable service levels during interventions. Such occurrences underscored the critical importance of detailed planning and proactive risk management for supply continuity and operational efficiency.

The relevance of this study therefore lies in the need to understand and mitigate the risks associated with the transition and modernization of supply systems in public institutions, which often operate with restricted budgets and legacy infrastructures. Sectorization, although promising, demands in-depth analysis of potential challenges to ensure its effectiveness and sustainability. Thus, this work aimed to identify, analyze, and classify the risks inherent in the implementation of water distribution network sectorization in a Brazilian public university, proposing, based on this analysis, mitigation strategies that contribute to improving the operational efficiency and safety of the institutional supply system, serving as a basis for similar projects.

2. Material and Methods

The research was classified as applied, exploratory and descriptive in nature, adopting a predominantly qualitative approach with quantitative analysis support, according to Gil (2019) guidelines. The exploratory character was justified by the scarcity of studies on risk management in the sectorization of water distribution networks in university environments, aiming to provide greater familiarity with the problem and refine hypotheses. Concurrently, the study assumed a descriptive profile, seeking to identify, classify, and characterize the identified risks, detailing their causes, consequences, and probability of occurrence. This approach allowed for an in-depth understanding of the investigated phenomenon.

The methodological strategy adopted was qualitative, based on the interpretive analysis of the Systematic Literature Review, institutional documentary analysis, and the collection of expert perceptions through a structured form. Complementarily, a quantitative treatment was incorporated through the application of a probability and impact matrix, following the guidelines of the Project Management Institute (PMI, 2021), which enabled the objective classification of identified risks. In terms of technical procedures, the research was configured as a case study, focusing on the sectorization of the water distribution network of a Brazilian public university, as recommended by Yin (2018).

The study was conducted at a Brazilian public university, whose campus underwent a significant transition in its water supply system starting in mid-two thousand and twenty-four. During this period, the institution implemented its own system based on tubular wells and a self-managed internal network, in response to regulatory and tariff changes. The internal distribution network, over fifty years old, had a history of recurring problems. The central unit of analysis was the university campus’s water distribution network, focusing on the risks associated with its sectorization.

The main unit of analysis was the university campus water distribution network. The population of interest for the systematic literature review included scientific articles published between two thousand and twenty and two thousand and twenty-six, in English, in the areas of Civil Engineering, Water Resources, Environmental Engineering, Operations Research, and related fields. Exclusion criteria covered articles unrelated to the objective, unavailable for access, or duplicates. For the field survey, the sample consisted of three specialists with technical or managerial roles directly linked to the institution’s supply system, selected for their experience and involvement with the distribution network.

Data collection was structured in three sequential and complementary stages, the results of which were triangulated for the identification and classification of risks. The first stage consisted of a Systematic Literature Review (SLR), conducted through a structured protocol, based on Dresch, Lacerda and Antunes Júnior (2015) and Galvão and Ricarte (2019). The search was carried out in the Web of Science database, using a specific search string and applying temporal, language, and category filters, as detailed in the protocol. This stage aimed to identify potential risks in the sectorization of water distribution networks.

Table 1. Protocol for Systematic Literature Review

Element

Description

Conceptual framework

Identify potential risks in the water distribution network sectorization

Context

Water distribution network risk management

Search Fields

Title, Abstract and Keywords

Search Filters

Temporal: 2020-2026
Language: English
Category: Civil Engineering, Water Resources, Environmental Engineering, Multidisciplinary Sciences, Operations Research, Management Science, Construction Technology and Management.
Document Type: Article

Keywords

Water distribution zoning, water distribution sectorization, sectorization and water distribution network

Search String

(“Water distribution zoning” OR “water distribution sectorization” OR sectorization) AND “water distribution network”

Database

Web of Science

Exclusion Criteria

Not related to the work objective
Not available for access
Duplicate Articles

Source

Original research results

Source: Original research results

The second stage involved institutional documentary analysis, with the purpose of characterizing the operational context and infrastructure of the university’s supply system. Technical reports, maintenance records, operational communications, and projects related to the implementation and operation of the proprietary supply system were examined. This analysis allowed for an understanding of the history of occurrences and the mapping of institutional vulnerabilities. The third stage comprised a survey of specialists, using a structured electronic form, developed on the Google Forms platform, to validate literature-based risks, identify new risks, and classify the probability and impact of each.

The research execution began with the Systematic Literature Review, where the search in the Web of Science database resulted in thirty-five initial records. After the rigorous application of the exclusion criteria defined in the protocol, ten articles were selected for full reading and summarization, providing the theoretical basis for the preliminary identification of risks. This stage was crucial for contextualizing the problem and supporting the construction of the data collection instrument with specialists, ensuring a robust foundation for subsequent analyses.

Next, a documentary analysis of the university was carried out, examining technical reports and operational records to characterize the supply system and identify historical vulnerabilities. This phase allowed for a deep understanding of the existing infrastructure and the history of occurrences, mapping critical points related to sectorization. Subsequently, the electronic form was sent to the specialists on March 4, 2026, with a response deadline of March 20 of the same year. The responses obtained were analyzed to validate the identified risks and collect new insights.

The collected data were submitted to a treatment and analysis process that involved the organization of identified risks into thematic categories. This categorization was consolidated from the triangulation of findings from the systematic literature review, documentary analysis, and expert perceptions. Responses to the open-ended questions of the form were analyzed qualitatively, using the content analysis technique to identify recurring perceptions and additional risks not previously contemplated, enriching the understanding of the risk scenario.

For the classification of risks, the probability-impact matrix was used, following the guidelines of the Project Management Institute (PMI, 2021). The probability of occurrence (P) and the potential impact (I) of each risk were measured on a scale of one to four, corresponding to the levels Low, Medium, High, and Very High, respectively. The final risk level was determined by the product of P by I. The results were then consolidated into a risk matrix, allowing the classification of events into Low, Medium, High, and Critical levels, providing an objective basis for prioritizing mitigation actions.

Based on the risk classification, especially those categorized as High and Critical, mitigation strategies were proposed. These strategies were developed in accordance with the risk response guidelines of the PMBOK (PMI, 2021), aiming to reduce the probability of occurrence, minimize the potential impact, or a combination of both. The mitigation plan sought to offer practical solutions aligned with good project management practices, contributing to the improvement of operational efficiency and the safety of the institutional supply system.

The research was conducted in strict compliance with the ethical principles applicable to academic studies, ensuring respect for copyright and bibliographic source citation standards. The electronic form applied to the specialists was designed not to request personal or institutional data that could identify the participants. Participation was voluntary, with prior acceptance, and anonymity and confidentiality of responses were assured, with data used exclusively for academic purposes and analyzed in an aggregated manner, without individualization of respondents.

To assess the need for submission to the Ethics in Research Committee, the institutional Ethical Guidance Form was completed. The result indicated that formal submission was not necessary, given the nature of the research and the absence of sensitive data collection or information that could identify participants. However, a relevant methodological limitation was the restricted participation of specialists to the managerial and planning segment, with the absence of professionals from the operational sector. This restriction may have limited the capture of practical and everyday perceptions about the network’s functioning, which could complement the strategic vision obtained.

3. Results and Discussion

Based on the triangulation between the analysis of institutional documentation, previous technical works related to the university’s water supply system, the systematic literature review, and the survey of specialists, it was possible to perform a comprehensive characterization of the context in which the internal distribution network was inserted, identify the risks associated with the proposed sectorization, and support the construction of the risk classification matrix. The following results and discussions detail these findings, contextualizing them with the relevant literature and exploring their practical implications.

The characterization of the university system revealed a scenario of transition and vulnerability. The university campus, the subject of this study, underwent a significant change in its water supply system, driven by the enactment of Law No. 14.026, of July 15, 2020, the new Legal Framework for Basic Sanitation. This legislation led to the concession of water supply and sewage services in the metropolitan region to a private operator, altering the contractual and tariff relationship with the university. The previous operator, which maintained differentiated tariffs, was replaced, and the new charges were considered incompatible with the institution’s budgetary reality. This situation forced university management to seek water self-sufficiency, implementing its own supply system based on tubular wells and an internally managed network starting in mid-2024.

This decision, although strategic for institutional autonomy and economy, brought with it an expansion of internal responsibility for risk management in water production and distribution. The Pro-Rectory of Infrastructure assumed the operation of the production system, composed of three tubular wells with periodic preventive maintenance, and the modernization actions of the distribution network. The production system, being new and monitored, presented a more controlled risk profile, focusing on guaranteeing water quality and hydraulic efficiency, in accordance with environmental conditions and applicable standards for the operation of underground intakes. However, the internal distribution network, over 50 years old, contrasted with this modernity. The coexistence of a recent production system and an aging distribution network configured an environment of expanded risk, where structural and operational fragilities manifested in episodes of pipeline ruptures and valve failures.

The literature corroborates that aging infrastructure is one of the main factors that aggravate the efficient management of urban water resources, especially in contexts of disordered growth and budgetary constraints (Tucci, 2008; UNESCO, 2020). Water losses, often caused by faulty or poorly maintained pipelines, can represent 20% to 30% of the transported water, reaching over 50% in old networks (El-Zahab and Zayed, 2019; Elshazly et al., 2024). In the university’s case, the need for temporary suspension of academic activities, rationing in specific sectors, and the use of water trucks to supply the university residence highlighted significant vulnerabilities in the system’s capacity to maintain acceptable service levels during interventions. This suggests risks associated with pressure management, coordination of operational maneuvers, and availability of reserves and supply alternatives, aspects that become even more critical in a network with a history of problems. The decision to seek self-sufficiency, although an opportunity for savings and control, placed sectorization in an environment of high structural vulnerability, where interventions could generate unforeseen effects, especially related to pressure management and supply continuity. The application of practices recommended by the Project Management Institute (PMI, 2021) for risk management therefore becomes fundamental to mitigate these challenges.

The Systematic Literature Review (SLR) was a crucial step to contextualize the problem and support the preliminary identification of risks. The search in the Web of Science database initially returned 35 results. After the rigorous application of the exclusion criteria defined in the protocol, 10 articles were selected for full reading and summarization, as illustrated in the PRISMA flowchart presented in Figure 1.

Figure 1. PRISMA flowchart of the literature search

Source: Original research results

The analysis of recent literature evidenced that, although the zoning of water distribution networks is widely recognized as an effective strategy for loss control, improvement of operational management, and increase of hydraulic efficiency, its implementation was associated with a relevant set of technical, operational, and institutional risks and difficulties. This finding is fundamental, as it demystifies the idea that zoning is a universally simple solution, revealing the complexity inherent in its application in real systems.

Studies based on optimization methods and graph theory, such as those by Vasilic et al. (2020, 2024) and Raimundo et al. (2023), have shown that the definition of sectors depends heavily on the quality and availability of hydraulic and consumption data, as well as on the adequate calibration of the models used. Solutions obtained by heuristic methods or evolutionary algorithms have proven sensitive to uncertainties in input data, especially in extensive and poorly monitored networks, resulting in hydraulically unbalanced or operationally weak sectors. This implies that, without precise cadastral survey and reliable consumption data, sectorization may not achieve its objectives of loss control and hydraulic optimization, and may even aggravate existing problems by creating zones of low pressure or overload. The practical implication for the university is the urgent need to invest in data collection and hydraulic modeling before any physical intervention, to avoid perpetuating inefficiencies.

Another recurring aspect in the literature referred to the high computational effort and complexity associated with the application of advanced techniques, such as “fuzzy” modularity maximization, multi-objective optimization algorithms, and digital twin-based approaches. Pandey and Srinivas (2025) and Ramos et al. (2024) discussed that the adoption of dynamic District Metered Areas and digital tools required automation, telemetry, and real-time communication infrastructure, in addition to skilled technical teams. This requirement limits the practical application of these solutions in systems with financial and institutional constraints, as is the case for many public universities. The university, therefore, faces the challenge of balancing technological ambition with the reality of its resources, suggesting an incremental and pragmatic approach to automation and monitoring, initially focusing on the most critical points of the network.

From a hydraulic point of view, the literature highlighted that sectors defined predominantly by topological criteria or graph metrics did not always guarantee adequate hydraulic performance. Spizzo et al. (2023) pointed out that excessive reduction of connections between sectors compromised network redundancy, increasing its vulnerability to failures and hindering operational maneuvers in emergency situations. This risk was shown to be amplified when main pipelines were included within sector boundaries, which, according to Zhou et al. (2021), increased the impact of failures and measurement costs, although their exclusion reduced the capacity for flow and pressure control. For the university, this means that sectorization must be carefully planned to maintain operational flexibility and the ability to isolate sections without compromising the supply to critical areas. Redundancy, often seen as an additional cost, is actually an investment in resilience, crucial for an institutional environment that cannot afford prolonged interruptions.

Additionally, post-sectorization efficiency evaluations, such as the one conducted by Palomero-González et al. (2022), have shown that poorly conceived sectors tended to perpetuate pre-existing problems, such as inadequate pressures, demand imbalances, and limitations arising from aging infrastructure. In these cases, sectorization, rather than acting as a solution, highlighted structural weaknesses of the system. This reinforces the need for the university’s sectorization project to be not just a technical intervention, but a comprehensive diagnostic and planning process that considers the current condition of the network and the specific needs of each sector, avoiding the replication or worsening of problems.

Finally, the integration of zoning with pressure management and energy recovery strategies, as discussed by Souza, Mesquita, and Blanco (2023) and Cemiloglu et al. (2023), introduced new challenges related to real-time control, sensitivity to demand variations, and the operational difficulty of adjusting and maintaining multiple regulating devices. These complex aspects require not only technology but also trained teams and robust operational protocols. The university, when implementing zoning, must be aware that the mere division of the network is not enough; it is necessary to develop an internal capacity for continuous management and maintenance to extract the maximum benefit from the new configuration.

The initial risk assessment, consolidated from the systematic literature review, documentary analysis, and expert perceptions, resulted in the identification of 22 risks, distributed across five categories: Internal Network Infrastructure, Supply Operation and Continuity, Water Production and Quality, Management, Coordination and Communication, and Sectorization Planning and Implementation. This breadth of categories underscores the complexity of the sectorization project and the need for a holistic approach to risk management.

In the Internal Network Infrastructure category, Risk R1: Rupture of pipelines during pressure variations or maneuvers was identified as a recurring problem. Old pipelines, over 50 years old, are inherently more susceptible to structural failures, especially under pressure stress or during operational maneuvers, which can generate pressure peaks. Elshazly et al. (2024) and El-Zahab and Zayed (2019) highlight that infrastructure age is a critical factor for the occurrence of leaks and ruptures, resulting in water waste, infrastructure damage, and supply interruption. The practical implication is the need for a gradual replacement program for older pipelines and the implementation of pressure control systems to minimize peaks.

The Risk R2: Failure of valves at critical isolation points also proved relevant. Old or poorly maintained valves can jam, leak, or burst, compromising the ability to isolate sectors and generating the need for emergency repairs. The literature on asset management in water networks emphasizes the importance of preventive maintenance and scheduled valve replacement to ensure system operability (Souza, Mesquita and Blanco, 2023). The failure of a valve at a strategic point can make sectorization unfeasible, rendering loss control and pressure management ineffective.

The Risk R3: Insufficient sector reservation capacity was another critical finding. Sectors with small or non-existent reservoirs may run out of water during scheduled maintenance or emergencies, increasing the risk of supply shortages in critical areas. Palomero-González et al. (2022) and Cemiloglu et al. (2023) discuss how reservation capacity is vital for system resilience, especially in segmented networks. The absence of adequate reserves necessitates longer interruptions and reliance on emergency solutions, such as water trucks, which are costly and inefficient.

In the Operation and Supply Continuity category, Risk R4: Total or partial interruption of supply during repairs was identified. Inadequate sectorization or poorly coordinated maneuvers can result in unforeseen interruptions, paralyzing essential activities and generating academic and administrative losses. Zhou et al. (2021) warn about the importance of detailed operational planning to avoid unnecessary interruptions. The complexity of a university network, with diverse buildings and uses, requires a robust contingency plan and effective communication to minimize impacts.

The Risk R5: Rationing in priority units during intervention periods highlights the vulnerability of laboratories, research centers, the university restaurant, and student housing. These units cannot suffer supply restrictions without significant impact on food safety, sanitation, and research activities. The lack of a clear prioritization protocol exacerbates this risk.

The Risk R6: Dependence on emergency solutions, such as the use of water trucks, was classified as an expensive and operationally unsustainable solution in the medium term. Cemiloglu et al. (2023) emphasize that the lack of adequate redundancy and reserve imposes high costs and operational inefficiencies, making the system dependent on external resources in times of crisis.

In the Water Production and Quality category, Risk R7: Reduction in well productivity due to maintenance failures was identified. Delays or inadequacies in preventive maintenance can lead to a drop in flow rate or interruption of production, generating supply deficits during peak hours and dependence on emergency solutions. The management of tubular wells requires a rigorous maintenance program to ensure the sustainability of the source.

The Risk R8: Non-compliance with environmental and regulatory conditions arises from inadequate monitoring or absence of operational adjustments, potentially resulting in non-compliance with environmental legislation, fines, and risk of loss of operational autonomy. By assuming the management of water production, the university also assumes the responsibility to comply with all legal and environmental requirements, which demands a robust monitoring and reporting system.

The Risk R9: Water quality variation due to failures or delays in preventive maintenance can cause variations in turbidity, iron, manganese, or other parameters, with risks to public health and the need for additional treatment. Spizzo et al. (2023) emphasize the importance of water quality for public health. The university needs to ensure periodic analyses and rapid corrective actions to maintain the potability of the distributed water.

In the Management, Coordination and Communication category, Risk R10: Internal communication failures regarding rationing and suspensions unnecessarily amplifies the impacts, compromising crisis management and deteriorating institutional trust. Clear, transparent, and timely communication is essential to manage user expectations and minimize panic in interruption situations.

The Risk R11: Lack of clear prioritization of critical loads leads to non-standardized decisions and disproportionate impacts in strategic areas. Zhou et al. (2021) highlight the importance of prioritization protocols to optimize resource distribution in scarcity scenarios. The absence of a formal plan can generate conflicts and inefficiencies.

The Risk R12: Misalignment between intervention planning and academic calendar results in suspension of activities, with academic loss and impact on institutional image. Coordination between infrastructure teams and academic administration is vital to schedule maintenance during periods of lower impact, such as recesses.

Finally, in the Zoning Planning and Implementation category, Risk R13: Inadequate definition of zoning boundaries was identified. Sectors that are too large, heterogeneous, or have excessive interconnections make it difficult to control losses and manage pressure, compromising the efficiency of zoning. Raimundo et al. (2023) discuss how zoning optimization depends on well-defined hydraulic and topographic criteria.

The Risk R14: Absence or insufficiency of measurement points per sector limits the identification of losses and operational problems, making management reactive instead of proactive. Sela Perelman et al. (2015) emphasize that continuous flow and pressure measurement is fundamental for segmented monitoring and early leak detection. Without this data, sectorization operates in the dark.

The Risk R15: Lack of integration between sectorization and maintenance plan exposes critical sectors to unmanaged risks and concentrates vulnerabilities in strategic points. Sectorization must be a component of the maintenance plan, not an isolated initiative, to ensure that interventions are coordinated and effective.

The Risk R16: Loss of hydraulic redundancy after sectorization occurs when the isolation of sectors by closed valves reduces network interconnections, increasing the system’s vulnerability to failures. Souza, Mesquita, and Blanco (2023) and Spizzo et al. (2023) warn that sectorization should seek a balance between isolation and redundancy to maintain the capacity for rapid reconfiguration in emergencies.

Risk R17: Imbalance of pressures between sectors due to poorly implemented sectorization or miscalibrated pressure-reducing valves results in excessive pressures in some sectors and insufficient pressures in others, increasing the risk of leaks and supply shortages. Palomero-González et al. (2022), Cemiloglu et al. (2023), and Zhou et al. (2021) discuss the importance of precise PRV calibration for optimizing hydraulic performance.

The Risk R18: High cost of measurement and automation infrastructure is a significant challenge. The implementation of meters, motorized valves, and automation systems requires substantial investment, often incompatible with the budget of public institutions, resulting in partial or inadequate sectorization. Ramos et al. (2024) and Cemiloglu et al. (2023) highlight that the feasibility of sectorization depends on the institutional capacity to invest in infrastructure and technology.

The Risk R19: Difficulty in optimizing algorithms for old networks arises from the irregular characteristics of networks over 50 years old (variable diameters, mixed materials, uncontrolled pressures), which hinder the application of modern optimization algorithms, resulting in suboptimal sectorization. Raimundo et al. (2023) and Ramos et al. (2024) address the complexity of modeling and optimizing historical networks.

The Risk R20: Vulnerability to isolated failures in critical nodes occurs when inadequate sectorization creates single points of failure whose rupture affects multiple sectors simultaneously, generating widespread supply interruption. Souza, Mesquita, and Blanco (2023) emphasize the importance of identifying and protecting these critical nodes.

Finally, Risk R21: Need for specialists for calibration and operation is an obstacle. The absence of qualified technical personnel at the university hinders the implementation and operation of sophisticated sectorization, generating dependence on external consultants. Ramos et al. (2024) and Zhou et al. (2021) point to team training as a critical success factor.

The Risk R22: Inconsistency between the planned sectorization and the physical topography of the network, including unmapped interconnections, was the only one classified as Critical. This risk, with a PxI level of 16, highlighted a recurring limitation pointed out in the literature: the difficulty of translating theoretical or computational solutions to real systems with complex physical characteristics and a history of unrecorded modifications (Raimundo et al., 2023). The perception of the consulted experts corroborated this finding, with unmapped interconnections being pointed out as the main obstacle to the success of sectorization. This result reinforced the need for adaptive approaches that consider not only optimization criteria but also the operational and structural constraints of the existing system. The lack of precise knowledge of the underground infrastructure is a common problem in old networks and can make any sectorization project unfeasible, as simulations and planning are based on incomplete or incorrect data.

The analysis of the specialists’ responses was fundamental to validate, complement, and deepen the risks identified in the previous stages, giving the study an empirical perspective anchored in the practical experience of the professionals directly involved with the institution’s supply system. Regarding the respondents’ profile, the three participating professionals work in the areas of management, planning, and technical inspection of the institutional water infrastructure, with between one and three years of experience directly related to the distribution network. Although the operational sector did not respond to the form within the established deadline — as noted in the limitations of this research —, the profile obtained proved relevant for the strategic and planning analysis of the identified risks. This limitation, however, may have restricted the capture of practical and daily perceptions about the network’s operation, which could complement the strategic vision obtained. It is recommended that future studies broaden the scope of the survey, incorporating the perspective of field operators for a more comprehensive characterization of the identified risks.

Regarding infrastructure and supply continuity, the specialists corroborated the risks raised in the literature and documentary analysis. The university restaurant and the university residence were unanimously pointed out as the most critical sectors of the network, due to their essentiality for serving the academic community, making them vulnerable to interruptions. This perception aligns with risks R3 (Insufficient reservation), R4 (Total/partial interruption), and R5 (Rationing in priority units), which deal, respectively, with insufficient reservation capacity, supply interruption during repairs, and rationing in priority units. The absence of a defined protocol for prioritizing sectors in situations of water restriction was confirmed by the three respondents, reinforcing risk R11 (Lack of clear prioritization of critical loads) and highlighting an operational governance gap that could compromise decision-making in emergencies.

Regarding the production system, experts confirmed that the system has sufficient redundancy between wells to maintain production in case of unit failure, which represents a positive resilience factor and partially mitigates risks R7 (Drop in well productivity) and R20 (Vulnerability to isolated failures in critical nodes). However, two respondents indicated that preventive maintenance does not always occur as planned, which supports the classification of risk R7 and points to the need for a more structured maintenance plan. Preventive maintenance is a fundamental pillar for the sustainability of any supply system, and its neglect can quickly compromise the university’s water self-sufficiency.

Regarding the zoning planning, the data revealed relevant divergences among the respondents. Two specialists confirmed the existence of updated distribution network projects, while one indicated that these projects only exist partially. More definitively, two of them indicated that the hydraulic zoning model was not fully built. This inconsistency corroborates risks R13 (Inadequate definition of sector limits), R14 (Absence or insufficiency of measurement points per sector), and R22 (Topographic inconsistency/interconnections), signaling that the available database for zoning planning presents gaps that can compromise the quality of the proposed solutions, as pointed out by Raimundo et al. (2023) and Ramos et al. (2024). The lack of a complete and updated hydraulic model is a significant impediment to any effective zoning project, as it prevents accurate simulation of network behavior and identification of optimization points.

The availability of financial resources for investment in zoning also generated divergent perceptions: one expert confirmed the existence of resources, another denied it, and the third declared uncertainty. This uncertainty reinforces risks R18 (High cost of measurement and automation infrastructure) and R21 (Need for specialists), corroborating the findings of Ramos et al. (2024) and Cemiloglu et al. (2023), who highlight financial and institutional restrictions as limiting factors to the full implementation of zoning in public systems. Project management in public institutions frequently faces budgetary challenges, which requires creativity in seeking funding and an incremental approach to implementing improvements.

Regarding open-ended responses, experts identified the main consequences of poorly planned sectorization as: water losses, pressure problems, poor network management and control, difficulty in identifying leaks, and compromised water quality. These perceptions converge directly with risks R13, R16, R17, and R19, reinforcing the relevance of the risks mapped in the literature. A risk considered more critical by the experts was the existence of unmapped interconnections in the network, pointed out by one of the respondents as the main obstacle to the success of sectorization. Another expert highlighted the inadequate sizing of the system as a central risk, emphasizing that the absence of a detailed hydraulic diagnosis can compromise the entire logic of sectorization. Both perceptions converge towards risk R22 — inconsistency between planned sectorization and the physical topography of the network —, classified as the only Critical risk in the matrix, with a PxI level equal to 16. This result aligns with Raimundo et al. (2023), who warn about the difficulty of transposing computational solutions to real systems with complex physical characteristics and a history of unrecorded modifications.

As a priority mitigation strategy, the experts converged on conducting a detailed hydraulic and cadastral diagnosis of the network before the definitive implementation of sectorization, including topographic survey, identification of existing interconnections, hydraulic modeling using specialized software such as EPANET or WaterCAD, and careful definition of sector limits. This recommendation directly supports the mitigation strategies proposed for High and Critical risks, presented in the following section. Finally, all experts recognized the importance of installing flow and pressure meters per sector to identify losses and operational problems, validating risk R14 (Absence or insufficiency of measurement points per sector) and reinforcing that continuous monitoring is an essential condition for the effectiveness of sectorization. The unanimity on this point highlights that, regardless of disagreements on resources and planning, there is consensus among professionals regarding the need for adequate instrumentation as a prerequisite for more efficient and proactive water management.

The 22 identified risks were consolidated in the probability-impact matrix presented in Table 2, prepared according to the PMBOK guidelines (PMI, 2021). The resulting classification indicated one critical risk, 12 high risks, five medium risks, and four low risks, demonstrating a predominantly high vulnerability profile in the analyzed context.

Table 2. Risk classification matrix

Code

Risk

Category

P

I

PxI

Classification

R1

Pipe rupture

Infrastructure

2

4

8

Average

R2

Valve failure

Infrastructure

3

3

9

High

R3

Insufficient reservation

Infrastructure

3

4

12

High

R4

Total/partial interruption

Operation

2

4

8

Average

RFI

Rationing in priority units

Operation

3

4

12

High

R6

Tank truck dependency

Operation

1

3

3

Low

R7

Well productivity decline

Production/Quality

1

3

3

Low

R8

Environmental non-compliance

Production/Quality

3

3

9

High

R9

Water quality variation

Production/Quality

2

3

6

Average

R10

Internal communication failures

Management

1

3

3

Low

R11

Lack of prioritization of critical loads

Management

2

3

6

Average

R12

Misalignment with academic calendar

Management

1

2

2

Low

R13

Inadequate definition of sectors

Sectorization

3

4

12

High

R14

Absence of measurement by sector

Sectorization

3

4

12

High

R15

Lack of integration with maintenance

Sectorization

3

3

9

High

R16

Loss of hydraulic redundancy

Sectorization

3

4

12

High

R17

Pressure imbalance

Sectorization

3

4

12

High

R18

High cost of automation

Sectorization

4

3

12

High

R19

Optimization difficulty in old networks

Sectorization

3

3

9

High

R20

Vulnerability in critical nodes

Sectorization

2

4

8

Average

R21

Need for specialists

Sectorization

3

3

9

High

R22

Topographical inconsistency/interconnections

Sectorization

4

4

16

Critical

Source: Original research results

The analysis of the results showed that the risks associated with the zoning of the water distribution network on the studied campus were not restricted to purely technical aspects, but reflected a combination of structural weaknesses, operational limitations, and institutional challenges. This finding was aligned with the literature, which points out that the effectiveness of zoning depends not only on the techniques employed, but on their integration with the real conditions of the system and the operational capacity of the organization (Raimundo et al., 2023; Ramos et al., 2024). The complexity of a university supply system, with its old infrastructure and the varied demands of a community, requires a multifaceted approach that transcends mere hydraulic engineering.

The application of the Pareto Diagram to the obtained risk levels, presented in Figure 2, revealed that to achieve 80% of the system’s accumulated criticality, it was necessary to consider the first 14 risks ordered by decreasing level — which corresponds to 64% of the identified risks. This result indicates that the criticality distribution in the analyzed system did not follow the typical concentration pattern of the 80/20 rule, but was relatively uniform among the identified categories.

Figure 2. Pareto diagram with risk prioritization

Source: Original research results

Such a finding constitutes, in itself, a relevant result: unlike systems where few risks dominate total vulnerability, the studied campus revealed a distributed vulnerability profile, in which multiple categories and dimensions of the system contributed expressively to the global risk. This pattern reinforces the need for comprehensive and structured risk management throughout the entire project lifecycle, and not just punctual or restricted to a subset of critical events, in full accordance with the PMBOK guidelines (PMI, 2021). The absence of a clear concentration of risks means that the university cannot focus its mitigation efforts on just one or two problems, but must implement a risk management plan that addresses all categories systematically and continuously.

It was observed that risks classified as High and Critical were predominantly concentrated in the categories of planning and implementation of network zoning and infrastructure, which reinforced the argument that old and poorly monitored networks tended to present greater sensitivity to interventions, as discussed by Spizzo et al. (2023) and Palomero-González et al. (2022). In the analyzed case, the coexistence between a recent production system and an aging distribution network intensified this scenario, increasing the probability of failures during operational maneuvers and pressure adjustments. The existing physical infrastructure imposes significant restrictions on the planning and execution of zoning, and the lack of precise data on this infrastructure further exacerbates the problem.

Of particular note was risk R22 — inconsistency between the planned sectorization and the physical topography of the network, including unmapped interconnections —, classified as the only Critical risk in the matrix, with a PxI level equal to 16. This result highlighted a recurring limitation pointed out in the literature: the difficulty of transposing theoretical or computational solutions to real systems with complex physical characteristics and a history of unrecorded modifications (Raimundo et al., 2023). The perception of the consulted experts corroborated this finding, with unmapped interconnections being identified as the main obstacle to the success of sectorization. This result reinforced the need for adaptive approaches that consider not only optimization criteria but also the operational and structural constraints of the existing system. The absence of an updated and accurate network registry is a fundamental bottleneck that prevents the effective application of any sectorization methodology, as simulations and planning are based on an incomplete or incorrect representation of reality.

From the perspective of Project Management, the results indicated that sectorization should be treated as a high-complexity project, in which risk management plays a central role throughout the entire lifecycle. According to the Project Management Institute (PMI, 2021), the identification, analysis, and response to risks are fundamental processes for increasing the probability of project success. In the case studied, the predominance of risks classified as High and Critical, combined with the uniform distribution of criticality among categories, suggested that, without structured planning and active risk management, the implementation of sectorization could not only fail to achieve its objectives but also aggravate pre-existing problems in the network. Risk management, therefore, is not a mere appendix, but an intrinsic and continuous component of the entire sectorization process, from the conception phase to operation and maintenance.

The presence of risks related to institutional communication (R10), prioritization of critical loads (R11), and misalignment with the academic calendar (R12) showed that the challenges were not exclusively technical, but also organizational. These findings reinforced the importance of integration between technical and administrative areas and the adoption of project governance practices, as recommended by the PMBOK (PMI, 2021), especially in the planning and stakeholder engagement processes. Sectorization, in a university environment, cannot be seen solely as an engineering project, but as an initiative that impacts the entire community and requires interdepartmental coordination to minimize disruptions and ensure the continuity of academic and administrative activities.

The limitation of financial and human resources, evidenced in the risks related to the cost of automation (R18) and the need for qualified specialists (R21), corroborated the findings of Ramos et al. (2024) and Cemiloglu et al. (2023), who highlighted that the viability of sectorization depended directly on the institutional capacity to invest in infrastructure, technology, and technical training. In public institutions, these restrictions tended to be even more significant, which required prioritization and incremental implementation strategies, an approach consistent with the principles of progressive planning advocated by the PMBOK (PMI, 2021). The university, with its budgetary and personnel constraints, needs to adopt a phased approach, prioritizing interventions with the greatest impact and seeking solutions that optimize the use of available resources, perhaps through partnerships or external funding.

Finally, the results suggested that zoning, although widely recognized as an effective strategy for loss control, should not be understood as an isolated solution. Its effectiveness depended on integration with maintenance policies, pressure management, continuous monitoring, and strategic planning. In this sense, risk management presented itself as a structuring element, capable of guiding decision-making and increasing the system’s resilience to the uncertainties inherent in the analyzed operational environment. Zoning should be part of a broader water infrastructure management program, which includes network modernization, team training, and the implementation of monitoring technologies.

Based on the classification obtained in the risk matrix, mitigation strategies were proposed for the 13 risks, 12 classified as High and for the single Critical risk, as presented in Table 3. The adopted strategies followed the risk response guidelines of the PMBOK (PMI, 2021), contemplating the approaches of mitigate, avoid, and accept, selected according to the nature and feasibility of intervention on each risk.

Table 3. Plan for Mitigation of Critical and High Risks.

Code

Risk

Classif.

Mitigation Action

Responsible

Deadline

R22

Topographical inconsistency and unmapped interconnections

Critical

Perform a complete hydraulic and cadastral diagnosis of the network before implementing sectorization, including topographic survey, identification of all existing interconnections, and hydraulic modeling in specialized software (EPANET or WaterCAD).

Pro-Rectory of Infrastructure / Specialized Technical Consultancy

Short term

R13

Inadequate definition of sector boundaries

High

Define sector boundaries based on hydraulic, topographic, and demand criteria, using computational modeling calibrated with real data from the institutional network.

Engineering technical team / Specialized consulting

Short term

R14

Absence or insufficiency of measurement points per sector

High

Plan and install flow and pressure meters at strategic points in each sector, prioritizing critical sectors (RU, residence, laboratories), with integration to a continuous monitoring system.

Pro-Rectory of Infrastructure / Maintenance Sector

Medium term

R16

Loss of hydraulic redundancy after sectorization

High

Design the zoning while preserving strategic interconnections between sectors, ensuring alternative supply routes in emergency or maintenance situations.

Engineering technical team

Short term

R17

Pressure imbalance between sectors

High

Install and calibrate pressure reducing valves (PRVs) at critical points in each sector, with continuous monitoring and periodic adjustments according to demand variations.

Pro-Rectory of Infrastructure / Operation Sector

Medium term

R18

High cost of measurement and automation infrastructure

High

Adopt an incremental implementation model, prioritizing critical sectors in the first phase and gradually expanding as budgetary availability allows. Evaluate external funding sources (FNDE, parliamentary amendments).

Institutional Management / Planning Pro-Rectory

Long term

R3

Insufficient reservation capacity of the sectors

High

Evaluate and expand the reservation capacity of critical sectors, ensuring a minimum volume of autonomous supply for scheduled or emergency maintenance periods.

Pro-Rectory of Infrastructure

Medium term

RFI

Rationing in priority units during interventions

High

Develop a formal protocol for prioritizing critical sectors (RU, residence, laboratories, IT), with standard operating procedures for water restriction situations.

Pro-Rectory of Infrastructure / University Management

Short term

R2

Valve failure at critical sectioning points

High

Implement a periodic preventive inspection and maintenance program for shut-off valves, with scheduled replacement of components at the end of their useful life.

Maintenance Department

Short term

R8

Non-compliance with environmental and regulatory conditions

High

Structure the environmental monitoring routine according to the licensing body’s conditions, with systematic recording of operational parameters and periodic compliance reports.

Pro-Rectory of Infrastructure / Environmental Advisory

Short term

R15

Lack of integration between zoning and maintenance plan

High

Develop an integrated preventive maintenance plan aligned with the sectorization project, identifying priorities by sector and establishing a schedule compatible with the academic calendar.

Maintenance Department / Pro-Rectory of Infrastructure

Medium term

R19

Difficulty of optimizing algorithms for old networks

High

Adopt an iterative and adaptive approach in sectorization, with progressive calibration of the hydraulic model from field-collected data, revising sector boundaries as needed.

Specialized technical consulting / Engineering team

Medium term

R21

Need for specialists for calibration and operation

High

Empower the institutional technical team through specific training in the operation of sectorized systems and hydraulic modeling, progressively reducing dependence on external consultants.

Pro-Rectory of Infrastructure / Institutional HR

Medium term

Source: Original research results

Risk R22 (Topographical inconsistency/interconnections), classified as Critical, demanded priority and immediate action, being associated with the mitigation strategy through the execution of a complete hydraulic and cadastral diagnosis of the network before the implementation of sectorization. This action was corroborated by the perception of the consulted specialists, who pointed to unmapped interconnections as the main obstacle to the project’s success, and is aligned with the recommendations of Raimundo et al. (2023), who emphasize the need for detailed knowledge of the network’s physical characteristics as a prerequisite for any sectorization intervention. The absence of accurate records and a calibrated hydraulic model is a fundamental impediment to any sectorization project, as decisions would be based on incomplete or incorrect data, leading to suboptimal solutions or even greater problems. The initial investment in data collection and modeling is, therefore, an indispensable prerequisite for the project’s success.

For High risks, the proposed actions were organized into three temporal horizons. In the short term, priority was given to planning and prevention actions, such as the careful definition of sector limits (R13), the development of a critical load prioritization protocol (R5), preventive maintenance of valves (R2), and the structuring of an environmental monitoring routine (R8). The clear definition of sector limits, based on hydraulic, topographic, and demand criteria, is essential to ensure the effectiveness of sectorization in controlling losses and managing pressure. The creation of a critical load prioritization protocol ensures that, in situations of water restriction, the most sensitive areas of the university (such as laboratories and student housing) receive priority supply, minimizing academic and social impacts. Preventive maintenance of sectional valves is crucial to ensure the ability to isolate sections of the network, facilitating repairs and minimizing interruptions. Finally, the environmental monitoring routine ensures compliance with regulations and the quality of water produced by the wells.

In the medium term, infrastructure and capacity building actions were concentrated, including the installation of meters by sector (R14), pressure control via reducing valves (R17), the expansion of storage (R3), the integration between sectorization and maintenance plan (R15), and the training of the technical team (R21). The installation of flow and pressure meters at strategic points in each sector is vital to transform management from reactive to proactive, allowing for early identification of losses and operational problems. Pressure control through calibrated PRVs optimizes hydraulic performance, reducing leaks and the risk of ruptures. The expansion of storage capacity in critical sectors increases system resilience, ensuring autonomous supply during maintenance. The integration of the sectorization plan with the maintenance plan ensures that interventions are coordinated and vulnerabilities are managed holistically. The training of the institutional technical team is fundamental to reduce dependence on external consultants and build internal capacity for managing and operating sectorized systems.

In the long term, the incremental implementation of measurement and automation infrastructure (R18) was proposed as a strategy to reconcile technical needs with the budgetary constraints characteristic of public institutions. This approach recognizes that significant investments in technology may not be feasible all at once, but can be carried out in phases, prioritizing the most critical sectors and gradually expanding as budgetary availability allows. The search for external funding sources, such as FNDE or parliamentary amendments, is also an important strategy to enable these long-term investments.

In general, the mitigation plan showed that most of the required actions did not depend exclusively on high financial investments, but on institutional organization, integrated planning, and the adoption of structured operational protocols — factors fully accessible to university management and consistent with the project governance practices advocated by PMBOK (PMI, 2021). This is particularly relevant for public institutions, which often operate with limited budgets. The emphasis on governance, planning, and internal capacity building demonstrates that significant advances in Risk Management can be achieved through a strategic and systematic approach, without depending exclusively on large financial contributions. Risk Management, therefore, emerges as a pillar for the sustainability and efficiency of the university’s water supply system, ensuring the continuity of services and the water security of the academic community.

4. Conclusion

It is concluded that the objective was achieved by identifying, analyzing, and classifying the risks inherent in the implementation of water distribution network sectorization in a Brazilian public university. The study mapped 22 risks into five categories, with 13 classified as High and one as Critical, highlighting the inconsistency between planning and the physical topography of the network, including unmapped interconnections (R22), as the main challenge. The analysis revealed a distributed vulnerability profile, reinforcing the need for comprehensive and continuous Risk Management, in line with PMBOK guidelines. The proposed mitigation strategies, organized into short, medium, and long-term time horizons, demonstrated that most priority interventions depend more on institutional organization and integrated planning than on high financial investments, which is crucial for public institutions with restricted budgets.

Despite the breadth of the findings, the study presented as a limitation the restricted number of participating specialists, which may have influenced the diversity of perceptions, especially regarding the operational perspective. For future studies, it is suggested to deepen quantitative approaches for risk analysis, the practical implementation of the proposed mitigation strategies, and the validation of the results in a real environment. Such initiatives will contribute to the continuous improvement of risk management and to the strengthening of maturity in project management in the context of institutional water management, serving as a valuable subsidy for similar projects in other public universities.

Bibliographic References

Dresch, A.; Lacerda, D.P.; Antunes Júnior, J.A.V. 2015. Design science research: método de pesquisa para avanço da ciência e tecnologia. Bookman, Porto Alegre, RS, Brasil.

El-Zahab, S.; Zayed, T. 2019. Leak detection in water distribution networks: an introductory overview. Smart Water 4(1): 1–9. https://doi.org/10.1186/s40713-019-0021-3

Elshazly, D. et al. 2024. An automated geographical information system-based spatial machine learning method for leak detection in water distribution networks (WDNs) using monitoring sensors. Applied Sciences 14(13): 5853. https://doi.org/10.3390/app14135853

Galvão, T.F.; Ricarte, I.L.M. 2019. Manual para redação de revisões sistemáticas.

Gil, A.C. 2019. Métodos e técnicas de pesquisa social. 7 ed. Atlas, São Paulo, SP, Brasil.

Pandey, J.; Srinivas, V.V. 2025. Fuzzy membership based weighted modularity maximization approach for sectorization of water distribution network into dynamic district metered areas. Journal of Water Resources Planning and Management.

Project Management Institute (PMI). 2021. A guide to the project management body of knowledge (PMBOK® Guide). 7 ed. Project Management Institute, Newtown Square, PA, USA.

Raimundo, S.D.C.; Pastich, E.A.; Bezerra, S.D.M. 2023. Efficient approach for the sectorization of water distribution systems: integrating graph theory and binary particle swarm optimization. Water Resources Management.

Ramos, H. M. et al. 2024. Smart water grids and digital twin for the management of system efficiency in water distribution networks. Water 16(3): 412.

Saldarriaga, J. et al. 2025. Phased methodology for the optimal rehabilitation of a network with an intermittent water supply based on hydraulic criteria. Journal of Water Resources Planning and Management 151(6).

Sela Perelman, L. et al. 2015. Automated sub-zoning of water distribution systems. Environmental Modelling & Software 65: 1–14. https://doi.org/10.1016/j.envsoft.2014.11.012

Spizzo, F.; Venaruzzo, G.; Nicolini, M.; Goi, D. 2023. Water distribution network partitioning based on complex network theory: the Udine case study. Water 1

Tucci, C.E.M. 2008. Águas urbanas. Estudos Avançados 22(63): 97–112.

UNESCO. 2020. Relatório mundial das Nações Unidas sobre o desenvolvimento dos recursos hídricos 2020: água e mudanças climáticas. UNESCO, Paris, França.

Vasilic, Z.; Babic, B.; Ivetic, D.; Kapelan, Z.; Stanic, M. 2024. An improved DeNSE methodology for optimal sectorization of water distribution networks. Water Resources Management.

Vasilic, Z.; Stanic, M.; Kapelan, Z.; Prodanovic, D.; Babic, B. 2020. Uniformity and heuristics-based DeNSE method for sectorization of water distribution networks. Water Resources Management 34: 2217–2234.

Yin, R.K. 2018. Case study research and applications: design and methods. 6 ed. Sage, Thousand Oaks, CA, USA.

Article originating from the Final Course Work of the Specialization in Project Management of the MBA USP/Esalq

To learn more about the course, click here and access the MBX Academy platform

You may also like

Executive Mba In Leadership And Management

November 23, 2026

Improvements in the efficiency of a secondary biological sludge drying plant

The management of industrial solid waste, especially secondary biological sludge, represented an operational and strategic challenge for a company in the pulp and paper sector. A secondary biological sludge drying plant, installed to meet environmental requirements and reduce costs, operated with low efficiency and high unavailability. The objective of this study was to evaluate and propose a set of actions to increase the operational availability of the plant, ensure the integral processing of the generated sludge, and reduce treatment and transportation costs, in addition to mitigating environmental risks. To this end, an analysis of the root causes of low efficiency was carried out, using tools such as the cause-and-effect diagram (Ishikawa) and the “5 whys” analysis, and hypotheses were tested to identify the most impactful factors. Three main root causes were identified: addition of low-load effluent to the process, absence of a dedicated maintenance team, and lower consistency of dewatered sludge. The proposed countermeasures, which included stopping the addition of effluent, hiring a maintenance team, and testing polymers, had a monthly implementation cost of R$ 35,000.00. An annual reduction in operating expenses of up to R$ 1,800,000.00 and maintenance costs of R$ 600,000.00 was estimated, in addition to a 25% reduction in operational unavailability. It was concluded that the proposed measures are viable, quick to implement, and capable of ensuring the integral processing of secondary biological sludge, strengthening the company’s ESG strategy and ensuring environmental compliance.

Keywords: Operational costs; Operational efficiency; ESG; Biological sludge; Sludge drying.

Data Science And Analytics For Operations

November 19, 2026

Polyp-YOLO: an efficient, low-latency detector for polyps in colonoscopies

The early detection of colorectal polyps is crucial for the prevention of colorectal cancer, and real-time computer-aided detection (CADe) systems have shown gains in endoscopic practice. The objective was to develop and validate a lightweight colorectal polyp detector, based on the YOLO architecture, capable of operating on restricted hardware with high precision and low latency. The methodology used public datasets of endoscopic images, partitioning the Kvasir-SEG dataset for training and internal validation, and CVC-ClinicDB and ETIS-Larib Polyp DB for cross-dataset evaluation. Lightweight variants of the YOLOv8, YOLO11, and YOLO26 families with 640×640 pixel input were evaluated. A grid search tested 70 combinations of optimizers and activation functions, and identified AdaBelief and LeakyReLU as the configuration with the best generalization. The optimization pipeline applied unstructured pruning, knowledge distillation, and fine-tuning. The optimized YOLO11n-seg model outperformed the higher-capacity architecture (YOLO26m-seg) in mAP50 and showed similar performance in F1-Score, operating with approximately seven times fewer parameters. It achieved an mAP50 of 0.7929 and an F1-Score of 0.7514 on the ETIS-Larib dataset, and fast inference was demonstrated in different formats, with real-time latencies. The explainability of predictions was validated by Grad-CAM activation maps. The proposed solution demonstrated itself to be a promising experimental tool for diagnostic support, with technical feasibility for integration into environments with reduced computational power, although it requires future clinical validation.

Keywords: Computer-aided detection; Edge computing; Hyperparameter optimization; Endoscopic image segmentation; Medical computer vision.

Data Science And Analytics For Operations

November 19, 2026

Multi-touch Attribution in E-commerce: A Comparison between Markov Chains and Last-Click

The research investigated Multi-touch Attribution (MTA) Models in e-commerce, seeking to overcome the limitations of the Last-Click model, widely used in the market. The objective was to compare the performance of first-order Markov Chains with Last-Click and Position-Based approaches, identifying the value of assistance channels frequently ignored. To this end, Markov Chain algorithms were applied to a large volume of purchase journey data from the Google Merchandise Store, extracted via BigQuery. The study probabilistically mapped the purchase journey and calculated the Removal Effect to quantify channel relevance. The results demonstrated that data-driven models identified the strategic role of discovery (awareness) and assistance channels, which Last-Click neglected in 65% of complex journeys. Simulated financial analysis indicated an approximate 28% hidden efficiency in Cost Per Acquisition (CPA) for Paid Search, compared to the Last-Click model. It was concluded that Markov Chains allowed for a more accurate mapping of purchase journeys, validating the technical feasibility of the modeling and providing evidence for more efficient budget allocation in digital media, mitigating the risk of early divestment in crucial channels.

Keywords: Assistance channels; Data science; E-commerce; Digital marketing; Media optimization.

Project Management

November 19, 2026

Integrated Software for Operational Communication and Control: Practical Evidence in a Medium-Sized Company

The study analyzed the impacts of the lack of integration between commercial and operational modules of an integrated management software (ERP/CRM) in a medium-sized company in the mechanical engineering sector. The main objective was to evaluate practical evidence of communication and operational control optimization, identify bottlenecks, and formulate improvement proposals. A qualitative-quantitative approach was adopted through a single case study with documentary research, based on the extraction and filtering of historical task records from the Bitrix24 software and statistical correlation analysis between workload and allocated team. Based on the diagnosis, an action plan structured in the 5W2H tool was developed. The results revealed that 54.4% of the registered tasks consisted of duplicate, test, or practically useless records, generated by manual insertion during the scope transition between commercial CRM and engineering. It was also demonstrated that the increase in the commercial team linearly accompanied the growth of inefficient tasks, polluting the database and masking the organization’s real productive capacity. It was concluded that the automation of workflows and native integration between modules are essential to mitigate operational and financial risks, providing replicable guidelines for data governance in small and medium-sized enterprises.

Keywords: System Customization; Enterprise Resource Planning (ERP); Task Management; Management Software.

Project Management

November 19, 2026

Supervised learning in voltammetric quantification with electrochemical sensors

The application of supervised learning in the voltammetric quantification of paraquat in artificial urine was evaluated. The study aimed to quantitatively assess the predictive performance of supervised learning models compared to a univariate “baseline”, preserving independence between devices in the training and testing sets. The research was conducted as an applied case study, processing data from four physical devices, each evaluated under a blank condition and six paraquat concentration levels, totaling 28 square wave voltammetry (SWV) curves. A computational “pipeline” integrated automated file reading, organization of curves into current-potential matrices, generation of potential maps, and device-specific blank correction. Five approaches were considered: conventional univariate calibration, predictive univariate “baseline”, partial least squares (PLS) regression, support vector regression (SVR), and random forest (RF). Predictive evaluation was performed using device-grouped cross-validation. PLS showed the best predictive performance for curves from a device not used in training, with an R² of 0.7981. RF exhibited intermediate performance, while SVR and the predictive univariate “baseline” showed inferior and similar performance between themselves. It was concluded that a compact multivariate representation of the voltammetric profile was more favorable for inter-device prediction than increasing model flexibility under the studied conditions. Grouped validation preserved independence, but the limited number of devices restricts the generalization of results.

Keywords: Supervised learning; Paraquat; PLS; Electrochemical sensors; Square wave voltammetry.

Project Management

November 19, 2026

Improvement of Inventory Management via Lean Six Sigma: Study in the Paper Industry

Organizations seek methodologies to reduce waste, increase efficiency, and become more competitive, promoting sustainable improvements in their processes. In this context, the study aimed to apply the Lean Six Sigma methodology, through the DMAIC cycle, to improve inventory management in a company in the paper industry manufacturing pneumatic hoses, aiming to increase the accuracy between physical and systemic inventories and improve the visual management of parts storage. The research was developed from the collection and analysis of data extracted from the company’s ERP system. Tools such as SIPOC, Ishikawa Diagram, and 5 Whys were used to define and identify the root cause of the problem. As improvement proposals, a Digital Kanban system and an adaptation of the Two-Bin system, called the Three-Bin System, were implemented, in addition to the development of standardized operating procedures and the establishment of control mechanisms. The results demonstrated a significant improvement in inventory accuracy, raising the lowest identified index from 28% to 80%, and detected discrepancies between systemic and physical records equivalent to R$ 134,335.53. It was concluded that the application of Lean Six Sigma, combined with Project Management, represented an effective approach for conducting operational improvement projects, contributed to increased reliability of inventory information, to the improvement of material control processes, and to the strengthening of the organization’s operational management.

Keywords: Inventory accuracy; DMAIC; Visual management.

Data Science And Analytics For Operations

November 19, 2026

Predictive Analysis Methodology for Performance Optimization in E-commerce: Correlation between Public Data and Paid Media

A predictive analysis methodology was developed for e-commerce, integrating transactional data and public search trends. The objective was to develop and validate a predictive model, based on machine learning algorithms, capable of correlating organic search trends with sales performance and paid media costs in the Beauty and Health category of Brazilian e-commerce. The Brazilian E-Commerce Public Dataset by Olist and data from Google Trends were used, processed in Python with the Random Forest Regressor algorithm. A moderate inverse correlation (r = -0.43) with a seven-day lag was identified between organic search volume and purchase. Initial models, based solely on behavioral variables, presented insufficient metrics (R² = -0.47; MAE of R$ 2,120.54). The incorporation of microeconomic (average ticket and shipping) and macroeconomic (exchange rate and Ibovespa index) variables raised the R² of the final model to 0.29, with an MAE of R$ 1,489.63, representing a 24.7% reduction in error compared to the baseline. Temporal cross-validation showed that, in periods of mature operation (2018), the model achieved an R² of 0.42. It was concluded that isolated search volume explains the moment of consumer interest, but not the financial magnitude of sales, making the fusion with transactional and economic data mandatory for predictive viability.

Keywords: Beauty and Health; Consumer Behavior; Google Trends; Machine Learning; Time Series.